A few years ago in the Dallas/Fort Worth area Texas, I was brought in by a forensic engineer on a corporate housing development, after a building inspector flagged concerns with cavity wall tie installation.
We carried out a density check using a metal detector, and found there were many missing wall ties.
When we opened up the wall, we found these two examples… just a small sample of a much bigger problem.
The cavities were designed to be 1 inch wide, but in reality, they were closer to 3 inches. The cavity on the left was bridged with brick debris, completely compromising its function.
The one on the right, the wall tie had been installed vertically, and neither nail on the ties had been driven fully into the wooden stud.
We inspected 28 houses that had similar issues.
I was contracted to wall tie all the houses with remedial stainless steel wall ties, and learnt a lot about wall tying American houses in the process!